Customization: | Available |
---|---|
Operating Temperature: | -40~70 ºC |
Usage: | HVAC Refrigeration etc. |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Product model
|
MH-711A
|
Detection gas
|
Carbon dioxide
|
Operating voltage
|
4.5 to 5.5V DC
|
Mean current
|
< 100 mA
|
Interface level
|
3.3V
|
Measuring range
|
Optional in the range of 0 to 5%Vol (see Table 2)
|
Output signal
|
IIC
|
|
0.4 to 2 V
|
Preheating time
|
3 min
|
Response time
|
T90 < 30 s
|
Operating temperature
|
-40 ~ 70
|
Working humidity
|
0 ~ 95% RH (no condensation)
|
Overall dimension
|
Φ44 mm x 61 mm
|
weight
|
350 g
|
Life span
|
> 5 years
|
Explosion-proof mark
|
Ex d C T6 Gb
|
Protection class
|
IP65
|
Gas name
|
Molecular formula
|
Range
|
Accuracy
|
Remarks
|
Carbon dioxide
|
CO2
|
02000 ppm
|
±(50 ppm+5% reading value)
|
Temperature compensation
|
|
|
06000 ppm
|
|
|
|
|
01% Vol
|
±(50ppm+ 5% read value)
|
|
Carbon dioxide
|
CO2
|
03% Vol
|
|
|
|
|
05% Vol
|
|
|